MCT 5091 Corrosion Inhibitor for Potable Water Systems

MCT 5091 is a liquid Zinc/Ortho Phosphate product that is designed to provide corrosion protection in potable water systems. The ingredients in MCT 5091 act to inhibit corrosion by forming a protective, microscopic film on metal surfaces. This film acts as a barrier to minimize the release of iron, lead, copper, and other metals that can produces harmful effects in the system. Also, red water problems that result from corrosion is greatly reduced or eliminated.

MCT 5091 is composed of ingredients accepted by the National Sanitation Foundation (NSF) for use in potable water supplies. MCT 5091 is approved for maximum use to 20 mg/L in the system. Also, the raw materials are recognized as safe (GRAS) according to the provisions in the Code of Federal Register.

Direction for Use:

MCT 5091 should be fed proportional to water flow. An initial starting dosage of approximately 10-11 gallons MCT 5091 per million gallons of system water is recommended. Typical dosage residuals range from 0.5-2.0 ppm phosphate by orthophosphate test procedure. Increase or decrease dosage depending on severity of system conditions. Test kit code 3114 for orthophosphate is recommended.

Product Data:

Form

Liquid

Product pH

1.29

Phosphate/zinc ratio

1:1

Specific Gravity

1.265

Weight/Gallon

10.5

Freeze Point

16°F

Handling:

MCT 5091 is an acidic solution. DO NOT GET IN EYES, ON SKIN OR ON CLOTHING. Use with adequate ventilation. Avoid breathing vapors. In case of contact, immediately flush eyes or skin with large amounts of water for at least 15 minutes. Call a physician.

Product Storage:

DO NOT allow product to freeze.

Available Packaging:

5 gallon pail

53 lbs.

15 gallon drum

158 lbs.

30 gallon drum

315 lbs.

55 gallon drum

578 lbs.

Test kit 3114-01 recommended